Large Eddy Simulation of Motion-Induced Contaminant Transports in Room Compartments

ORAL

Abstract

Large eddy simulation (LES) of contaminant transports due to complex human and door motions is conducted for characterizing the effect of the motion-induced wakes on the contaminant transports in room compartments where a contaminated and clean room are connected by a vestibule. We utilize a LES technique with an immersed-boundary method for moving objects (Choi et al., JCP 2007; Choi and Edwards, Indoor Air 2008) and extend the technique to include Eulerian descriptions of gas-phase contaminant transport as well as thermal energy transfer. We demonstrate details of contaminant transport due to human- and door-motion induced wake development during a short-duration event involving the movement of a person (or persons) from a contaminated room, through a vestibule, into a clean room. Parametric studies that capture the effects of human walking pattern, door operation, over-pressure level, and vestibule size are systematically conducted. The results of parameteric studies will be shown in the final presentation.

Authors

  • Jung-il Choi

    Dept. CSE, Yonsei University

  • Jack Edwards

    Dept. MAE, North Carolina State Univ.